TCMP
400 ºC / 2h centrifugal single-inlet extractor fans for outdoor operation in fire risk zones.
Fan:
- Sheet steel casing.
- Impeller with forward-curved blades made of galvanised sheet steel.
- Approved in accordance with standard EN 12101-3, with certificates numbers : 0370-CPR- 0313.
Motor:
- Class F motors with ball bearings and IP55 protection.
- IE3 efficiency motors for powers equal to or greater than 0.75kW except single-phase, 2-speed and 8-pole.
- Three-phase 230 / 400V ‐ 50 Hz (up to 4kW) and 400 / 690V ‐ 50 Hz (powers higher than 4kW).
- Maximum temperature of air to be carried : S1 continuous operation -20 ºC +250 ºC, S2 operation 300 ºC / 2h and 400 ºC / 2h.
Finish:
- Anti-corrosive finish of polyester resin polymerised at 190 ºC, previously degreased with phosphate-free nanotechnological treatment.