CO2-1 SENSOR

APPLICATION

  • The sensor is designed for indoor carbon dioxide concentration measurement and respective air capacity regulation through the control output signal to the fan.
  • Air capacity control based on CO2 concentration is an efficient energy saving solution.

 

TECHNICAL SPECIFICATIONS

  • Power supply / Consumption : 24VAC (50/60Hz ± 10 %), 24VDC / max. 1.6 W.
  • Gas sensing element : Non-dispersive infrared detector (NDIR) with self-calibration system.
  • CO2 measuring range : 0 - 2.000 ppm (parts per million).
  • Accuracy at 25 °C, 2.000 ppm : ± 30 ppm + 3 % of reading.
  • Response time : < 2 minutes.
  • Warm up time for each turning-on : 2 hours (first time) / 2 minutes (operation).
  • Analogue output : 0 - 10VDC (default), 4 - 20mA selectable by jumpers.
  • On/Off output : 1 x 2A switch load. Four set points selectable by jumpers.
  • 6 LED lights :

1st green indicator lights when CO2 concentration is below 600 ppm.

1st and 2nd green indicators light when CO2 concentration is 600 - 800 ppm.

1st yellow indicator lights when CO2 concentration is 800 - 1.200 ppm.

1st and 2nd yellow indicators light when CO2 concentration is 1.200 - 1.400 ppm.

1st red indicator lights when CO2 concentration is 1400 - 1600 ppm.

1st and 2nd red indicators light when CO2 concentration is above 1.600 ppm.

  • Operation conditions/ Storage regulations : 0 - 50 °C, 0 - 95% RH non condensing / 0 - 50 °C.
  • Net weight / Dimensions :120 g / 100 mm × 80 mm × 30 mm.
  • Mounting standard : 65 mm × 65 mm wire box, or hang on a nail.
  • Standard Approval : CE.